2023-05-20 12:17:11

Reasons for inverter low voltage trip


1. The low voltage of the inverter mainly refers to the low voltage of the intermediate DC circuit. Generally, the reason for the low voltage of the intermediate DC circuit comes from two aspects:


(1) Low voltage from the power input side


Under normal circumstances, the power supply voltage is 380V, and the allowable error is -15%~10%. After three-phase bridge full-wave rectification, the intermediate DC voltage value is 513V. In some cases, the power line voltage is small and the voltage fluctuation will not be The low voltage trip of the inverter will only cause the inverter to operate if the effective value of the grid voltage is between 80% and 85% of the rated value and the duration exceeds one cycle. The low voltage on the input side of the power supply is mainly due to the fluctuation of the grid voltage or the switching of the main power line, the power supply sine wave amplitude is affected by the lightning strike, the transformer of the power plant itself is overloaded or the load is unbalanced, etc.


(2) Low voltage from the load side


The reasons for this are mainly the start-up and application of large equipment, line overload, or starting large motors. The frequency converter is composed of rectifier and inverter. Through the research of the inverter, the low voltage of the inverter refers to the low voltage of the middle DC loop (that is, the input voltage of the inverter is too low). General frequency converters have protection functions of overvoltage, loss of voltage and instantaneous power failure. The inverter device of the inverter is divided into GTR and IGBT. When the inverter device of the inverter is GTR, once the voltage is lost or the power is cut off, the control circuit will stop outputting the signal to the drive circuit, so that the drive circuit and GTR all stop working, the motor It will be in free braking state. When the inverter device is IGBT, after the voltage loss or power failure, the inverter will be allowed to continue to work for a short time td. If the voltage loss or power failure time is totd, the inverter will protect itself and stop running. Generally, td is between 15 and 25 ms, and the power supply “shaking” time is generally more than a few seconds. The inverter will protect itself and stop running, so that the motor stops. Therefore, to solve the problem of inverter low voltage trip can not start from the inverter's inherent time td and voltage loss time to, but must start from the amplitude of the voltage drop.


2. Solutions for inverter low voltage trip:


There are two key points to be solved to solve the problem of inverter low voltage trip:


(1) It is necessary to select the inverter with IGBT inverter device;


(2) It is necessary to select the inverter that can still work normally under the condition of large voltage loss.


The motor can rotate, but the running current exceeds the rated value, which is called overload. The basic reflection of overload is that although the current exceeds the rated value, the magnitude of the excess is not large, and generally a large inrush current is not formed.


The reason and inspection method of inverter overload trip


1. The main reason for inverter overload


(1) Malfunction, the current detection part inside the inverter fails, and the detected current signal is too large, causing a trip.


(2) The mechanical load is too heavy. The main feature of the heavy load is that the motor heats up and can be found by reading the running current from the display.


(3) The three-phase voltage is unbalanced, which causes the operating current of a certain phase to be too large, resulting in overload tripping. It is characterized by unbalanced motor heating, which may not be found when the operating current is read from the display (because the display only shows one Phase current).


2. Check method of whether the inverter is overloaded


(1) Check whether the three-phase voltage on the motor side is balanced. If the three-phase voltage on the motor side is unbalanced, then check whether the three-phase voltage on the output side of the inverter is balanced. If it is not balanced, the problem is within the inverter.


If the voltage at the output of the inverter is balanced, the problem lies in the line from the inverter to the motor. Check whether the screws of all terminals are tightened. If there is a contactor or other electrical appliances between the inverter and the motor, It should be checked whether the terminals of the related electrical appliances have been tightened and the contact conditions of the contacts are good.


If the three-phase voltage on the motor side is balanced, you should understand the operating frequency at the time of tripping: if the operating frequency is low and vector control (or no vector control) is not used, first reduce the U/f ratio, if it can still drive the load , It means that the original preset U/f ratio is too high, the peak value of the excitation current is too large, and the current can be reduced by reducing the U/f ratio;


If the load can not be moved after the reduction, you should consider increasing the capacity of the inverter; if the inverter has vector control function, the vector control method should be used.


(2) Check whether the motor heats up. If the temperature rise of the motor is not high, first check whether the electronic thermal protection function of the inverter is preset properly. If the inverter still has a margin, the preheating of the electronic thermal protection function should be relaxed. Set value.


If the temperature rise of the motor is too high, and the overload is normal overload, it means that the motor is overloaded. At this time, whether the transmission ratio should be properly increased to reduce the load on the motor shaft. If it can be increased, increase the transmission ratio. If the transmission ratio cannot be increased, the capacity of the motor should be increased.


General purpose frequency converter


label

QR code

The public,

Mobile station
The public, Mobile station

Contact

未標題-8.png 0755-81719517
未標題-10.png0755-81719530 未標題-11.pngamb@ambition.com.cn
未標題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

Navigation

Home          About

Product      Case

Solution      Service

Job      News

Contact          

Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
主站蜘蛛池模板: 亚洲人在线 | 国产在线拍揄自揄拍无码视频 | 一级毛片超级播放 | 国产精品人成A片一区二区 蜜桃网站入口在线进入 | 日本黄色动漫网站 | 亚洲 欧美 变态 国产 另类 | 日本特级a一片免费观看 | 成人在线播放网址 | 欧美男生射精高潮视频网站 | 国产男人的天堂 | 蜜桃视频免费在线 | 成人动漫网站在线 | 成年无码动漫AV片在线尤物 | 欧美丰满白嫩bbwbbw | 精品无码国产AV一区二区三区 | 欧美久久影院 | 91亚色在线观看 | 天天干天天操天天好逼 | 丰满少妇猛烈进入三区视频 | 欧美区一区二区 | 中文字幕乱码中文乱码51精品 | 久久精品国产亚洲AV嫖农村妇女 | 榴莲视频黄色软件 | 婷婷激情图片久久 | 亚洲婷婷一区二区三区 | 日本性爱动漫 | 日本大片免费看 | 国产精品国产三级在线 | 在线国产能看的 | 免费的av网站在线观看 | 超碰超碰在线观看 | 日本xxxxxxxxxxxxxxxxxxxx | 国产六区| 午夜插插 | 顶级欧美熟妇XX | 日老女人的逼 | 逼特逼视频网站 | 国产第一页无线好源 | 国产精品igao视频网网址 | 艳母免费版| 午夜夜伦鲁鲁片免费无码 |